Turck 1 Channel Galvanic Barrier, Temperature Measuring Amplifier, RTD, Potentiometer, Thermocouple, Voltage Input,
- RS Stock No.:
- 808-6566
- Mfr. Part No.:
- IM34-14EX-CDRI
- Brand:
- Turck
Available to back order for despatch 25.11.2024
Price Each
Kr. 6 709,23
(exc. VAT)
Kr. 8 386,54
(inc. VAT)
Units | Per unit |
---|---|
1 + | Kr. 6 709,23 |
- RS Stock No.:
- 808-6566
- Mfr. Part No.:
- IM34-14EX-CDRI
- Brand:
- Turck
Technical Reference
Legislation and Compliance
- COO (Country of Origin):
- DE
Product Details
Temperature Measuring Amplifier
Professional range of galvanically isolated Temperature Measuring Amplifier, designed to evaluate the differential temperature - dependant changes within a variety of RTDs & thermocouples. This series is environmentally versatile and comes with a variety of approvals, meaning the IM signal conditioning series can be installed in a comprehensive range of applications
Features of the IM Temperature Measuring Amplifier Range
Suitable for installation into zone 2 environments
Complete galvanic isolation
Rotary coding switch allows adjustment of upper & lower limits
4 - 20mA output circuit with limit value relay output
Supports PT100 & Ni100 RTDs, types B E J K L N R S and T thermocouples
Internal or external cold junction compensation
Suitable for installation into zone 2 environments
Complete galvanic isolation
Rotary coding switch allows adjustment of upper & lower limits
4 - 20mA output circuit with limit value relay output
Supports PT100 & Ni100 RTDs, types B E J K L N R S and T thermocouples
Internal or external cold junction compensation
Standards
ATEX, IECEx, FM, UL, GOST
Turck Banner DIN Rail Mounting
Specifications
Attribute | Value |
---|---|
Number of Channels | 1 |
Module Type | Temperature Measuring Amplifier |
Barrier Type | Galvanic Barrier |
Output Signal Type | Current |
Interface | HART |
Hazardous Area Certification | ATEX, IECEx |
Input Signal Type | RTD, Potentiometer, Thermocouple, Voltage |
Maximum Operating Temperature | +70°C |
Minimum Operating Temperature | -25°C |
Supply Voltage | 20 → 125 V dc, 20 → 250V ac |
Safety Voltage Maximum | 250 V |
Operating Temperature Range | -25 → +70°C |