- RS Stock No.:
- 229-9232
- Mfr. Part No.:
- BXNE3410E2
- Brand:
- GEORGIN
Available to back order for despatch 23.07.2024, delivery within 2 working days
Not available for next day delivery
Added
Price 1 Box of 1
Kr. 2 816,00
(exc. VAT)
Kr. 3 520,00
(inc. VAT)
Box(es) | Per Box |
1 + | Kr. 2 816,00 |
- RS Stock No.:
- 229-9232
- Mfr. Part No.:
- BXNE3410E2
- Brand:
- GEORGIN
Technical Reference
Legislation and Compliance
- COO (Country of Origin):
- FR
Product Details
The GEORGIN galvanically insulated interface is an associated intrinsic safety item of equipment that is installed in a safe zone or in zone 2 in an IP 54 housing, thanks to the Ex nA protection mode. Its mission is to limit the level of energy that may appear in an electric circuit routed through a potentially explosive area, whatever the connection established upstream.In addition to its energy-limiting function, its facilitates the use of signals in safe areas (e.g., relays), converts signals (e.g., 4/20 mA to 0-10V) or duplicates signals. Other functions are also available, such as the threshold relay or powering intrinsic safety.
Intrinsic safe power supply
IS output: non linear
LH/ U0=13V / I0=185mA / P0=1250mW
1 remote, control by 24V, 1 output
Option: without, clamp terminals
Power supply: 24/48 Vdc
DIN rail mounting housing
---------- ATEX / IECEx informations ----------
EC type examination certificate LCIE 02 ATEX 6104X
IECEx LCI 09.0013X certificate
[Ex ia] IIC (-20 °C < Ta < 60 °C)
Group II (surface) - category (1) G/D
Installation in safe zone
Barrier for equipment installed in zone 0,1,2 et 20,21,22
See leaflet for a safe use
IS output: non linear
LH/ U0=13V / I0=185mA / P0=1250mW
1 remote, control by 24V, 1 output
Option: without, clamp terminals
Power supply: 24/48 Vdc
DIN rail mounting housing
---------- ATEX / IECEx informations ----------
EC type examination certificate LCIE 02 ATEX 6104X
IECEx LCI 09.0013X certificate
[Ex ia] IIC (-20 °C < Ta < 60 °C)
Group II (surface) - category (1) G/D
Installation in safe zone
Barrier for equipment installed in zone 0,1,2 et 20,21,22
See leaflet for a safe use
Specifications
Attribute | Value |
---|---|
Number of Channels | 1 |
Barrier Type | Galvanic Barrier |
Maximum Voltage | 13V |
Hazardous Area Certification | ATEX |
Supply Voltage | 24V dc |
Maximum Operating Temperature | +60°C |
Minimum Operating Temperature | -20°C |
Maximum Current | 185mA |
Series | BXNE |
Operating Temperature Range | -20°C to 60°C |